| Ambient Temperature-°C |
0 ÷ +40 |
| Battery Ambient Temperature |
0 ÷ +25 |
| UPS Storage Temperature-°C |
-10 ÷ +70 |
| BATTERY storage temperature - °C |
-10 ÷ +60 |
| Relative humidity (non condensing) |
<95% |
| Altitude |
< 1000 mt (above sea level) |
| Power Derating for altitude >100m |
According to "IEC62040-3" |
| Ventilation |
Forced |
| Request cooling air volume- m3/h |
500 |
| Audible Noise Level (according to EN 50091) |
< 52 db |
| Storage time of battery without recharge (at 25°C) |
3 months |
| Protection degree |
IP 20 |
| EMC compatibility |
According to "EN50091-2" (CE label) |
| Paint |
RAL 7016 |
| Accessibility |
From front and from top |
| Installation |
10 cm from the wall |
| Dimensions (mm) |
L=450 |
| Weight (kg) (without battery) |
90-250 |
| Static load (kg/m2) |
310-854 |
| Input/Output cable connection |
From low |
| Movement |
With Wheels |
| Ambient storange and transportation conditions |
According to "IEC62040-3" |
| Standard design |
According to "EN50091" "IEC 62040", "ISO 14001" |
| Autonomia |
Minuti |
|
< Back | ^ Top
|